E.I. DUPONT DE NEMOURS & CO (INC) -- SUVA HP62 (R404A) -- -
=====================  Product Identification  =====================

Product ID:SUVA HP62 (R404A)
MSDS Date:03/24/1999
FSC:NIIN:Submitter:D DG
Status Code:A
=== Responsible Party ===
Company Name:E.I. DUPONT DE NEMOURS & CO (INC)
Address:1001 MARKET STREET
City:WILMINGTON
State:DE
ZIP:19898
Country:US
Info Phone Num:800-441-9442
Emergency Phone Num:800-441-3637
Resp. Party Other MSDS Num.:DU005612
Preparer's Name:DUPONT CHEMICALS
Chemtrec Ind/Phone:(800)424-9300
CAGE:18873
=== Contractor Identification ===
Company Name:E.I. DUPONT DE NEMOURS & CO
Address:1007 MARKET STREET
Box:City:WILMINGTON
State:DE
ZIP:19898
Country:US
Phone:800-441-7515;800-441-9442
CAGE:18873

=============  Composition/Information on Ingredients  =============

Ingred Name:PENTAFLUOROETHANE
CAS:354-33-6
= Wt:44.
Other REC Limits:NONE RECOMMENDED

Ingred Name:1,1,1-TRIFLUOROETHANE (HFC-143A)
CAS:420-46-2
RTECS #:KJ4110000
= Wt:52.
Other REC Limits:NONE RECOMMENDED

Ingred Name:1,1,1,2-TETRAFLUOROETHANE (HFC-134A)
CAS:811-97-2
= Wt:4.
Other REC Limits:NONE RECOMMENDED

=====================  Hazards Identification  =====================

LD50 LC50 Mixture:NONE SPECIFIED BY MANUFACTURER.
Routes of Entry: Inhalation:YES  Skin:YES  Ingestion:NO
Reports of Carcinogenicity:NTP:NO    IARC:NO	OSHA:NO
Health Hazards Acute and Chronic:INHALATION OF HIGH CONCENTRATIONS OF
    VAPOR IS HARMFUL & MAY CAUSE HEART IRREGULARITIES, UNCONSCIOUSNESS
    OR DEATH. INTENTIONAL MISUSE OR DELIBERATE INHALATION MAY CAUSE
    DEATH WITHOUT WARNING. VAPOR RED UCES OXYGEN AVAILABLE FOR
    BREATHING & IS HEAVIER THAN AIR. LIQUID CONTACT CAN CAUSE
    FROSTBITE.
Explanation of Carcinogenicity:PER MSDS: CARCINOGENICITY: NONE OF
    COMPONENTS PRESENT IN MATERIAL AT CONCENTRATIONS EQUAL TO/>0.1%
    LISTED BY IARC/NTP/OSHA/ACGIH AS CARCINOGEN.
Effects of Overexposure:OVEREXPOSURE TO VAPORS BY INHALATION MAY
    INCLUDE TEMPORARY NERVOUS SYSTEM DEPRESSION WITH ANESTHETIC EFFECTS
    SUCH AS DIZZINESS, HEADACHE, CONFUSION, INCOORDINATION & LOSS OF
    CONSCIOUSNESS. HIGHER EXPO SURES TO VAPORS MAY CAUSE TEMPORARY
    ALTERATION OF HEART'S ELECTRICAL ACTIVITY WITH IRREGULAR PULSE,
    PALPITATIONS OR INADEQUATE CIRCULATION; FATALITY FROM GROSS
    OVEREXPOSURE. CONTACT WITH LIQUID MAY CA USE FROSTBITE.
Medical Cond Aggravated by Exposure:INDIVIDUALS WITH PREEXISTING
    DISEASES OF THE CENTRAL NERVOUS OR CARDIOVASCULAR SYSTEM MAY HAVE
    INCREASED SUSCEPTIBILITY TO THE TOXICITY OF INCREASED EXPOSURES.

=======================  First Aid Measures  =======================

First Aid:INHALATION: IMMEDIATELY REMOVE TO FRESH AIR. KEEP PERSON
    CALM. IF NOT BREATHING GIVE ARTIFICIAL RESPIRATION. IF BREATHING IS
    DIFFICULT GIVE OXYGEN. CALL PHYSICIAN. SKIN: FLUSH WITH LUKEWARM
    WATER. DO  NOT USE HOT WATER. IF FROSTBITE HAS OCCURRED CALL
    PHSYICIAN. EYE:IMMEDIATELY FLUSH WITH PLENTY OF WATER FOR AT LEAST
    15MINS. CALL PHYSICIAN. INGESTION: NOT PROBABLE ROUTE, HOWEVER IN
    CASE OF ACCIDENTA L INGESTION CALL PHYSICIAN. NOTE TO PHYSICIAN:
    CATECHOLAMINES SUCH AS ADRENALINE & OTHER COMPOUNDS HAVING SIMILAR
    EFFECTS SHOULD BE RESERVED FOR EMERGENCIES & THEN ONLY USED WITH
    SPECIAL CAUTION.

=====================  Fire Fighting Measures  =====================

Flash Point:WILL NOT BURN
Autoignition Temp:Autoignition Temp Text:UNK
Extinguishing Media:AS APPROPRIATE FOR COMBUSTIBLES IN AREA.
Fire Fighting Procedures:COOL CYLINDER WITH WATER SPRAY OR FOG.
    SELF-CONTAINED BREATHING APPRATUS (SCBA) IS REQUIRED IF CYLINDERS
    RUPTURE & CONTENTS ARE RELEASED UNDER FIRE CONDITIONS. WATER RUNOFF
    SHOULD BE CONTAINED & NEUTR ALIZED PRIOR TO RELEASE.
Unusual Fire/Explosion Hazard:NOT FLAMMABLE UP TO 212F & ATMOSPHERIC
    PRESSURE. BUT MIXTURES IN HIGH CONCENTRATIONS OF AIR AT ELEVATED
    TEMPERATURE CAN BECOME COMBUSTIBLE AT AMBIENT TEMPERATURE. AS
    TEMPERATURE IS INCREASED, LOWER PR ESSURE (STILL > ATMOSPHERIC) CAN
    CREATE SAME EFFECT. THEREFORE PRODUCT SHOULD NOT BE MIXED WITH AIR
    UNDER PRESSURE.

==================  Accidental Release Measures  ==================

Spill Release Procedures:REVIEW FIREFIGHTING MEASURES &
    HANDLING/STORAGE SECTIONS BEFORE CLEANUP. USE APPROPRIATE PPE
    DURING CLEANUP. VENTILATE AREA WITH FORCED VENTILATION, ESPECIALLY
    IN LOW OR ENCLOSED AREAS WHERE VAPORS CA N COLLECT. REMOVE OPEN
    FLAMES. USE SELF-CONTAINED BREATHING APPARATUS (SCBA) FOR LARGE
    SPILLS OR RELEASES.
Neutralizing Agent:NONE SPECIFIED BY MANUFACTURER.

======================	Handling and Storage  ======================

Handling and Storage Precautions:AVOID BREATHING VAPOR. AVOID LIQUID
    CONTACT WITH EYES & SKIN. USE WITH SUFFICIENT VENTILATION. CONTACT
    WITH CHLORINE OR OTHER STRONG OXIDIZERS SHOULD BE AVOIDED. STORE IN
    CLEAN, DRY AREA. DO NOT HEAT  ABOVE 52C (125F).
Other Precautions:CONTACT OF WELDING OR SOLDERING TORCH FLAMES WITH
    HIGH CONCENTRATION OF REFRIGERANT CAN RESULT IN VISIBLE CHANGES IN
    SIZE & COLOR OF TORCH FLAMES. THIS EFFECT WILL ONLY OCCUR IN
    CONCENTRATIONS WELL AB OVE RECOMMENDED EXPOSURE LIMIT. THEREFORE
    STOP ALL WORK & VENTILATE TO DISPERSE VAPORS BEFORE USING  OPEN
    FLAMES.

=============  Exposure Controls/Personal Protection  =============

Respiratory Protection:UNDER NORMAL MANUFACTURING CONDITONS NO
    RESPIRATORY PROTECTION IS REQUIRED WHEN USING PRODUCT.
    SELF-CONTAINED BREATHING APPARATUS REQUIRED IF LARGE RELEASES
    OCCURS.
Ventilation:LOCAL EXHAUST SHOULD BE USED IF LARGE AMOUNTS ARE RELEASED.
    MECHANICAL VENTILATION SHOULD BE USED IN LOW OR ENCLOSED PLACES.
Protective Gloves:IMPERVIOUS GLOVES.
Eye Protection:CHEM SPLASH GOGGLES.
Other Protective Equipment:NONE SPECIFIED BY MANUFACTURER.
Work Hygienic Practices:NONE SPECIFIED BY MANUFACTURER.
Supplemental Safety and Health

==================  Physical/Chemical Properties  ==================

HCC:G3
Boiling Pt:=-46.5C, -52.F
Vapor Pres:182 PSIA @ 77F
Vapor Density:NP
Spec Gravity:1.05 @25C
pH:NOT PROVIDED
Viscosity:NOT PROVIDED
Evaporation Rate & Reference:>1, CL4=1.
Solubility in Water:NOT DETERMINED.
Appearance and Odor:SLIGHT ETHEREAL ODOR, LIQUEFIED GAS, CLEAR,
    COLORLESS.
Percent Volatiles by Volume:100
Corrosion Rate:NP

=================  Stability and Reactivity Data  =================

Stability Indicator/Materials to Avoid:YES
ACTIVE METALS, ALKALI OR ALKALINE EARTH METALS-POWDERED AL, ZN, BE,
    ETC.
Stability Condition to Avoid:AVOID OPEN FLAMES & HIGH TEMPERATURES.
Hazardous Decomposition Products:CAN DECOMPOSE BY HIGH TEMPERATURE (OPN
    FLAMES/GLOWING METAL SURFACES/ETC) FORMING HYDROFLUORIC ACID &
    POSSIBLY CARBONYL FLUORIDE. THESE MATERIALS ARE TOXIC & IRRITATING.
    CONTACT SHOULD BE AVOIDED.

===================  Toxicological Information	===================

Toxicological Information:BLEND IS UNTESTED. FOR HFC-125: INHALATION 4
    HR ALC: > 709,000 PPM IN RATS. NO OBSERVED EFFECT LEVEL: 50,000 PPM
    FOR HFC-134A: INHALATION 4 HR LC50: 567,000 PPM IN RATS, LOWEST
    OBSERVED ADVERSE EFFECT  LEVEL: 75,000 PPM. FOR HFC-143A:
    INHALATION 4 HR LC50: >540,000 PPM IN RATS.

=====================  Ecological Information  =====================

Ecological:AQUATIC TOXICITY: HFC-143A, 96 HR LC50, RAINBOW TROUT: > 40
    MG/L. HFC-134A: 48 HR EC50, DAPHNIA MAGNA: 980 MG/L, 96 HR LC50,
    RAINBOW TROUT: 450 MG/L.

====================  Disposal Considerations  ====================

Waste Disposal Methods:COMPLY WITH LOCAL, STATE AND FEDERAL
    REGULATIONS. RECLAIM BY DISTILLATION OR REMOVE TO PERMITTED WASTE
    DISPOSAL FACILITY.

===================  MSDS Transport Information  ===================

Transport Information:DOT INFORMATION: LIQUEFIED GAS, N.O.S.
    (PENTAFLUOROETHANE & TETRAFLUOROETHANE), 2.2, UN3163, NONFLAMMABLE
    GAS LABEL.

=====================  Regulatory Information  =====================

SARA Title III Information:SARA EHS & TOXIC: NO, SECTION 311/312
    CLASSIFICATION: PRESSURE.
Federal Regulatory Information:CERCLA HAZARDOUS MATERIAL: NO
State Regulatory Information:NOT PROVIDED

 Disclaimer (provided with this information by the compiling agencies):
 This information is formulated for use by elements of the Department
 of Defense.  The United States of America in no manner whatsoever,
 expressly or implied, warrants this information to be accurate and
 disclaims all liability for its use.  Any person utilizing this
 document should seek competent professional advice to verify and
 assume responsibility for the suitability of this information to their
 particular situation.